MEGGER DET4TC2 Earth Ground Tester

Product Description

MEGGER DET4TC2 Earth Ground Tester

CV. Syariftama Global Indonesia has a wide range of Megger products  – search by type, or model, or filter by brand to find the one you are after. If you still can’t find it contact us.
The DET4TC2 is simple to use with an interface that is easy to understand. To switch between tests, you simply use the rotary dial to choose which test type you want. You can then choose the frequency of the test using the Hz to switch between 94, 105, 111 and 128Hz modes and you can then change the overall voltage of the test procedure between 25/50V. There’s also a button for activating a backlight on the LCD screen, allowing you to see your measurements in poor lighting conditions. When that’s all done you simply press the test button to activate the test and gain readings.

Features MEGGER DET4TC2 Earth Ground Tester

  • 2, 3 and 4 wire testing without the use of shorting links
  • C and P stake automatic checking
  • Automatic noise evaluation with noise rejection at 40V peak to peak
  • No disconnect testing (ART) possible with optional ICLAMP
  • Stakeless testing with use of ICLAMP or VCLAMP
  • Resistance range of 0.01 to 200kΩ
  • Easy to use
  • Protective carry case built around tester
  • IP54 ingress protection against dust and water
  • Runs on 8 x AA batteries

Specification MEGGER DET4TC2 Earth Ground Tester

Ingress Protection IP54
 C Stake, P Stake and Noise Checks  Automatic
Noise Rejection 40V peak to peak
2 wire, 3 wire and 4 wire tests Yes with no shorting links required
No disconnect testing (ART) Yes, with ICLAMP
Stakeless Measurements Yes, with ICLAMP and VCLAMP
Instrument Output Voltage: ±25 V or ±50 V at 94 Hz, 105 Hz, 111 Hz and 128 Hz
Current: 4.5 mA or 0.45 mA or 0.045 mA
Ground Current Range with Clamp 0.5 mA to 19.9 A
Ground Current Accuracy 5% ±3 digits
Ground Voltage Range 0 to 100V AC
Ground Voltage Accuracy 2% ±2 V
Resistance Range 0.01 Ω to 200 kΩ
Resistance Accuracy 2P measurements: 2% ±3 digits
3P measurements: 2% ±3 digits
4P measurements: 2% ±3 digits
ART measurements: 5% ±3 digits
Stakeless measurements: 7% ±3 digits
Maximum Probe Resistance Rp limit: 200 kΩ (50 V output voltage)
Rc limit: 200 kΩ (50 V output voltage)
Limits reduced to 100 kΩ for 25 V output voltage
Limits reduced to 5 kΩ for 0.01 Ω resolution
Display 31⁄2 digit high contrast liquid crystal, backlit
Battery Type DET4TC2: 8 off AA (LR6) cells
DET4TCR2: 8 off AA (LR6) NiMH rechargeable cells
Operating Temperature Range -15 °C to +55 °C / 5 °F to 131 °F
Storage Temperature Range -40 °C to +70 °C / -40 °F to 158 °F
Safety Complies with the requirements of IEC 61010-1 100V CAT IV
between terminal pairs
EMC In accordance with IEC61326-1
Standards Compliance Complies with the requirements of KEMA K85B
Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems
up to 1000 V a.c. and 1500 V d.c. – Equipment for testing, measuring or monitoring of protective
measures”.
Part 1 – General requirements
Part 5 – Resistance to earth
Dimensions 203 mm x 148 mm x 78 mm (8 in x 5.8 in x 3 in)
Weight 1kg (2.2lb)