Product Description
MEGGER DET3TC 3 Terminal Earth Resistance Tester
CV. Syariftama Global Indonesia has a wide range of Megger products – search by type, or model, or filter by brand to find the one you are after. If you still can’t find it contact us.
The DET3TC is rated to IP54, making it a truly outdoor instrument. It is designed to meet stringent safety standards and is rated CAT IV 100V. The ground tester has been designed to be easy to use – a large selector switch makes selection of 2 or 3 pole tests easy with gloved hands – and the design makes the fitting of shorting links to perform 2-pole tests a thing of the past.
Features MEGGER DET3TC 3 Terminal Earth Resistance Tester
- Performs both 2 and 3 point testing
- ART (Attached Rod Technique) capability allows testing of the rod without the need for disconnection
- Interested? Please don’t hesitate to call us @0265 3171044 OR wa us @0812-9753-6324
- Performs leakage current measurements down to 0.5 mA with current clamp (sold separately)
- User-selectable test voltages of 25V and 50V
- Microprocessor control ensures improved error detection
- Clear warnings and error indicators help prevent test failure
- Simple one button operation for improved efficiency
- Noise rejection to 40V peak to peak allows for accurate testing in noisy environments
- Accuracy of 2% of reading enhances reliability of measurements
- Voltmeter enables measurements of ground voltage and increases operator safety
- Large LCD display with choice of digital or analog readout
- Rugged,weatherproof to IP54 case suitable for outdoor environments
- CAT IV 100V rating provides increased operator safety in outdoor environments
Specification MEGGER DET3TC 3 Terminal Earth Resistance Tester
Resistance Range | 0.01 to 2000 Ω autoranging |
Resistance Accuracy | 2P measurements: 2% ±3 digits 3P measurements: 2% ±3 digits ART measurements: 5% ±3 digits |
Maximum Probe Resistance | Rp limit: 100 kΩ (50 V output voltage) Rc limit: 100kΩ (50 V output voltage) Limits reduced to 50 kΩ for 25 V output voltage Limits reduced to 5 kΩ for 0.01 Ω resolution on 18 Ω range |
Earth Voltage | Range: 0 to 100 V Accuracy: 2% ±2 V |
2- and 3-Wire Test | Yes |
Ground Current Range (with Current Measuring Clamp) | 0.5 mA to 19.9 A |
Ground Current Accuracy | 5% ±3 digits |
Test Frequency | Frequency: 128 Hz Voltage: 25 V or 50 V, user selectable (factory setting 50 V) Current: 450 mA or 4.5 mA |
Noise rejection | Rejection: 40 V peak to peak Check: Automatic |
C Spike Check | Automatic |
P Spike Check | Automatic |
General Specifications | |
Temperature | Operating: -5 to 131°F (-15 to 55°C) Storage: 40 to 158°F (-40 to 70°C) Humidity: 95% RH non-condensing at 104°F (40°C) |
Display | LCD |
Terminals | 4 mm plug type (test leads) |
Battery | 8 x 1.5 V AA cell |
Battery Life | 3 hours, 700 consecutive tests |
Safety | EN61010-1 CAT IV 100 V |
Ingress Protection | IP54 |
EMC | Meets the requirements of EN61326-1:1998 for use in heavy industrial areas |
Dimensions | 8 x 5.7 x 3.2″ (203 x 148 x 78 mm) |
Weight | 2.2 lbs (1 kg) |