Features MEGGER MIT2500 High Voltage Hand-Held Insulation and Continuity Tester
- Ideal tester for high voltage electrical and industrial applications
- Performs insulation resistance tests up to 2.5 kV with 200 Gigaohms maximum resistance
- Interested? Please don’t hesitate to call us @0265 3171044 OR wa us @0812-9753-6324
- Stabilized insulation test voltage remains within specification
- Guard terminal allows for high accuracy at higher voltages
- Adjustable insulation test voltage from 50 V to 2500 V
- Single range, faster continuity testing from 0.01 ohm to 1 Megaohm
- Provides clear readout on digital display with large characters and analog arc
- Offers PI, DAR, and timed test modes
- Detects live voltages and inhibits insulation testing above user-selected thresholds
- Buzzer limit alarms may be set for continuity and insulation tests
- Test lock function holds insulation test on continuously
- Rechargeable options for mains and car charging
- Suitable for use on CAT IV applications and supply voltages to 600 V
Specification MEGGER MIT2500 High Voltage Hand-Held Insulation and Continuity Tester
Insulation | |
---|---|
Insulation Accuracy | 50 Volts: 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ 100 Volts: 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ 250 Volts: 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ 500 Volts: 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ 1000 Volts: 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ 2500 Volts: 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ Service Error: BS EN 61557-2 (2007). 50V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.5% 100V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3% 250V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3% 500V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3% 1000V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 11.5% |
Guard Terminal Performance | <5% erros on 500kΩ parallel circuit resistance with 100MΩ load |
Display Range | Analogue: 1GΩ full scale |
Short Circuit/Charge Current | 2mA +0 to -50% t EN 61557-2 (2007) (except 2500V) |
Terminal Voltage Accuracy | -0 +2% ±2V |
Test Current | 1mA at minimum pass values of insulation to a maximum of 2mA max |
Operation | EN61557: 0.10MΩ to 1.0GΩ |
Leakage Current Display | 10% ±3 digits |
Voltage | ±3% ±2 digits ±0.5% of rated voltage |
Timer Control | Countdown timer 60 seconds (adjustable to 10 minutes) |
Note | Above specs only apply when high quality silicone leads are used |