PCE-PA 8300 Phase Power Meter 3-Phase

Product Description

PCE-PA 8300 Phase Power Meter 3-Phase

The PCE-PA 8300 is a 3-Phase Power Meter featuring a durable enclosure, SD card memory, LCD graphic display and visible, effective and reactive power metering. The easy-to-use PCE-PA 8300 3-Phase Power Meter is the ideal tool for performing power and harmonic analysis and for measuring network capacity.

The PCE-PA 8300 is available for purchase in two different configurations:

Set 1: Includes 3 current clamps for measurements up to 1200 A AC
Set 2: Includes 3 flexible Rogowski coils for measurements up to 3000 A AC (additional cost)

Please select Set 1 or Set 2 before adding PCE-PA 8300 to your cart.

Features PCE-PA 8300 Phase Power Meter 3-Phase

  • Voltage measurement range 10 V … 600 V AC
  • Current measuring range 20 A … 1200 A AC (Set 1) or 30 A … 3000 A AC (Set 2)
  • Performance measurement range 0 kW … 9.999 MW (VA/VAR)
  • Simultaneous display of harmonics and waveforms
  • Graphical Phasor Diagram
  • Capture transients including dips, swells and outages
  • SD card memory
  • LCD graphic display
  • Durable cage
  • Compatibility with power clamps of various manufacturers
  • Customizable backup intervals, enabling long-term data collection
  • Measuring range auto setting (AC V)
  • Power efficiency, delay angle and frequency measurement
  • Apparent, effective, and reactive power measurement
  • Measurement of harmonic spectrum up to the 50th order

Specifications PCE-PA 8300 Phase Power Meter 3-Phase

Voltage Measurement (AC V)
Measurement Range Resolution Accuracy
10 V … 600 V (phase to neutral) 0.1 V ±(0.5% + 0.5V)
10 V … 600 V (phase to phase 0.1 V ±(0.5% + 0.5V)
Current Measurement (AC A) Set 1
Measurement Range Resolution Accuracy
20 A 0.001 A (< 10 A)
0.01 A (≥ 10 A)
± (0.5 % + 0.1 A)
200 A 0.01 A (< 100 A)
0.1 A (≥ 100 A)
± (0.5 % + 0.5 A)
1200 A 0.1 A (< 1000 A)
1 A (≥ 1000 A)
± (0.5 A + 5 A)
Current measurement (AC A) Set 2
Measurement range Resolution Accuracy
30 A 0.001 A (< 10 A)
0.01 A (≥ 10 A)
±(0.5 % + 0.1 A)
300 A 0.01 A (< 10 A)
0.1 A (≥ 10 A)
±(0.5 % + 0.5 A)
3000 A 0.1 A (< 1000 A)
1 A (≥ 1000 A)
±(0.5 A + 5 A)
Effective power
Measurement range Resolution Accuracy
0 KW … 9.999 KW 0.001 KW ±(1 % + 0.008 KW)
10 KW … 99.99 KW 0.01 KW ±(1 % + 0.08 KW)
100 KW … 999.9 KW 0.1 KW ±(1 % + 0.8 KW)
1 MW … 9.999 MW 0.001 MW ±(1 % + 0.008 MW)
Apparent Power
Measurement range Resolution Accuracy
0 KVA … 9,999 KVA 0.001 KVA ±(1% + 0.008 KVA)
10 KVA … 99.99 KVA 0.01 KVA ±(1% + 0.08 KVA)
100 KVA … 999.9 KVA 0.1 KVA ±(1% + 0.8 KVA)
1 VAT … 9,999 VAT 0.001 MVA ±(1 % + 0.008 MVA)
Reactive Power
Measurement range Resolution Accuracy
0 LEFT … 9,999 LEFT 0.001 LEFT ±(1% + 0.008 KAR)
10 LEFT … 99.99 LEFT 0.01 LEFT ±(1% + 0.08 KAR)
100 LEFT … 999.9 LEFT 0.1 LEFT ±(1% + 0.8 KAR)
1 MVAR … 9.999 MVAR 0.001 MVAR ±(1% + 0.008 MVAR)
Active Energy
Measurement range Resolution Accuracy
0 KWH … 9,999 KWH 0.001 KWh ±(2 % + 0.008 KWh)
10.00 KWH … 99.99 KWH 0.01 KWh ±(2 % + 0.08 KWh)
100.0 KWH … 999.9 KWH 0.01 KWh ±(2 % + 0.8 KWh)
1 MWH … 9.999 MWH 0.001MMh ±(2 % + 0.008 MWh)
Apparent Energy
Measurement range Resolution Accuracy
0 KVARH … 9.999 KVARH 0.001 kVARh ± (2 % + 0.008 kVARh)
10.00 KVARH … 99.99 KVARH 0.01 kVARh ±(2%+0.08KVARh)
100.0 KVARH … 999.9 KVARH 0.01 kVARh ±(2%+0.8KVARh)
1 MVARH … 9.999 MVARH 0.001 MVARh ± (2 % + 0.008 MVARh)
Power Factor
Measurement range Resolution Accuracy
0 … 1 0.01 ±0.04
Delay Angle
Measurement range Resolution Accuracy
-180° … +180° 0.1° ±1°
Frequency
Measurement range Resolution Accuracy
45 Hz… 65 Hz 0.1 Hz ± 0.1 Hz
Harmonic of AC Voltage at 50 / 60 Hz
Measurement range Resolution Accuracy
1 … 20th order 0.001 … 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 … 30th order 0.001 … 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 … 50th order 0.001 … 1 A
0.1 %
not specified
General specifications
Display 3.7 in / 94.0 mm point-matrix LCD (320 * 240 pixel) with LED background lights
Safety standards IEC1010CAT III 600V
Input resistance AC V 10 MOhm
Operating frequency of current clamp 40 Hz… 1 kHz
Tested operating frequency of current clamp 45 Hz… 65 Hz
Overload protection AC V
AC A
720 V RMS
1300 A with current clamp
Data Storage SD memory card
Refresh interval 1 second
Data logging function logging with real-time speed on SD memory card
Record interval 2 … 7200 seconds
Data output (only for live display on computer) per USB or RS232, depending on connection cable
Operating temperature 0° C … +50° C / 32° F … 122° F
Surrounding humidity < 80 % RH
8 x 1.5 V AA batteries
Voltage Supply 9 V adapter
Current Drain Measurement Device: 300 mA DC
current clamp: 34 mA DC
Maximum Wire Diameter 50 mm / 1.9 in
Weight Measurement Device: 948 g / 33.4 oz (incl. battery)
Current clamp: 467 g / 16.4 oz (incl. cable)
Dimensions Device: 225 mm x 125 mm x 64 mm / 8.8 in x 4.9 in x 2.5 in
Current clamp: 210 mm x 64 mm x 33 mm / 8.2 in x 2.5 in x 1.2 in
Clamp jaw: 86 mm / 3.3 in (exterior)

 


PCE-PA 8300 Datasheet


Original products. We are direct distributors of PCE.  Cheap prices and guaranteed quality, of course. can be sent to all regions of Indonesia.

In shipping the products that customers buy, we have previously checked to ensure the products are in good condition and ready to be sent.

 